 
            
              
                Critical Supplemental Fire Protection
              
              
                Fire hose rack units provide a means for occupants to fight insipient fires or to escape larger ones,
                while standpipes provide a connection for fire departments to hook up to, making these two of the most
                important types of fire protection in or on a building. And both require periodic inspection and
                testing, per NFPA 1962 and NFPA 14.
              
              
                Why Choose Commercial Fire for your Fire Hose and Standpipes
              
              
                With nationwide coverage and reliable technicians, we have you covered. Commercial Fire offers
                complete service and inspections in accordance with manufacturer guidelines, NFPA 1962, Standard for the Care, Use, Inspection, Service Testing, and
                  Replacement of Fire Hose, Couplings, Nozzles, and Fire Hose Appliances; Standard for the Installation of Standpipe and Hose Systems;
                and the local Authority Having Jurisdiction.
              
             
            
              
              
                
                  
Maintenance Schedule
                
                
                  In accordance with NFPA 25
                  Every Year
                  
                    - Hose valves
- Pressure gauges
- Valves (all types)
 
               
             
            
              
              
                
                  
The CF Inspection Process
                
                
                  Inspect
                  
                    - Cabinet to ensure it has no damage
Check
                  
                    - Hose, couplings, nozzle, & storage device
- Hose liner
- Hydrostatic test hose (as required)
- For hose obstructions
- For missing/damaged caps & plugs (FDC)
- For inlet debris & body damage (FDC)
- Lock is functioning properly on cabinet, if applicable
- Hose is connected to the rack, nipple or valve
- House rack has swing of minimum 90 degrees from main cabinet
- Safety seals are intact
- All warning labels and tags are visible
- No obvious signs of damage or corrosion to the hose valve
Verify
                  
                    - Hose current test psi
- Hose manufacture date
- Hose is intact with no breaks, holes, or tears
- Cabinet door is easy to open
- All valves, hose nozzles, fire extinguishers in building are easily accessible
- Operating instructions are legible
- Nozzle is not missing
 
               
             
            
              Commercial Fire is also available 24/7, should you need
              additional service. From replacing and repairing to
              installing new equipment, we're your total fire hose
              and standpipe service solution.